A wide-band lumped circuit model of the terminal and internal electromagnetic response of coaxially insulated windings mounted on a core

2003 
This paper presents a wide-band lumped circuit model of coaxially insulated windings mounted on a core. The polyphase model can be used to simulate the terminal and internal electromagnetic response in DryformerTM, a new oil-free power transformer, and similar electromagnetic power devices. The circuit parameters are based on geometrical and material data. The simulated frequency and transient response of the lumped circuit is compared to measurements on a 20 MVA 140/6.6 kV three-phase transformer of the DryformerTM type. The comparison shows that the model can be used to estimate resonance frequencies and transient overvoltages in the transformer, although the damping is not accurately modelled. The influence of the core is discussed and investigated.