Active Current-Limiting Control to Handle DC Line Fault of Overhead DC Grid
2019
To handle with the DC line faults in a DC grid, this paper proposed an active current-limiting controller for hybrid MMC. With this active current-limiting control strategy, the requirement of interruption current of DCCB will be significantly decreased, and the investment of DC grid will be reduced obviously. Firstly, the control architecture of active current-limiting controller is disclosed. To avoid the overvoltage of submodule capacitors during DC fault, a dynamic limiter for the reference value of the DC current controller is proposed. To decrease the peak of fault current, the feedforward controller of DC voltage is put forward. The decoupling controllability of the AC/DC voltage of hybrid MMC is disclosed. The current-limiting mechanism of the active current-limiting controller is analysis. Then, the validity of the active current-limiting control strategy is verified by RTDS.
Keywords:
- Correction
- Source
- Cite
- Save
- Machine Reading By IdeaReader
12
References
4
Citations
NaN
KQI