Pool boiling performance of enhanced tubes on low GWP refrigerants

2017 
Abstract Low GWP refrigerants have drawn increasing attention as an alternative to HFC refrigerants that are regulated as a leading cause of global warming. The present study was focused on R-1234ze(E) and R-1233zd(E) refrigerants among other alternative refrigerant candidates and experimented on three types of tubes, i.e., a plain tube and two type of enhanced tubes, in terms of pool boiling heat transfer performance. The investigation was conducted under the experimental condition at saturated temperatures 4.4 °C and 26.7 °C and heat flux of 10–50 kW/m 2 . The heat transfer coefficients of R-1234ze(E) and R-1233zd(E) for the plain tube showed approximately 10.8–19.0%, 54.1–62.8% lower than those of R-134a respectively. Also, the results were compared against the previous empirical correlations, which proved satisfactory predictability for all conditions. For the enhanced 1 tube, the heat transfer coefficients of R-1234ze(E) and R-1233zd(E) showed 9.8–14.0%, 60.0–75.0% lower than those of R-134a, while the heat transfer coefficients of R-1234ze(E) and R-1233zd(E) for enhanced 2 tube showed 13.3–17.9%, 39.5–43.7% lower than those of R-134a respectively.
    • Correction
    • Source
    • Cite
    • Save
    • Machine Reading By IdeaReader
    24
    References
    14
    Citations
    NaN
    KQI
    []