Field Test and Demonstrated Operation of 10.5 kV/1.5 kA HTS Fault Current Limiter

2007 
Superconducting fault current limiter (SFCL) is an attractive appliance for modern electrical power system. Institute of Electrical Engineering (IEE) at the Chinese Academy of Science (CAS) has successfully demonstrated a three-phase HTS bridge-type fault current limiter (FLC) at a substation in Hunan, China. The FCL suppressed the fault current below 635 A successfully in a 3-phase-to-ground short-circuit field test. Since August 2005, it has been going on a demonstrated long-term reliable operation for one year in the live 110 kV/10.5 kV substation.