The Effect of a Vertical Electric Field on the Surface Flashover Characteristics of a Bushing Model

2018 
High-voltage bushings play a crucial role in energy conveyance. Their specialized electric structure makes the bushing more vulnerable to surface discharge. However, the influence of a vertical electric field on the surface flashover of bushing structures remains unclear. To investigate this mechanism, four simplified bushing samples were built and the influence of pollution, leakage length, and the electric field component vertical to the dielectric surface on flashover properties of the bushing samples were tested. It was found that the surface pollution level was the decisive factor that influenced flashover voltage. When the leakage length and form factor were the same, the pollution flashover of the bushing structure was lower than that of the post structure. It was also found that increasing the leakage length was not very effective in improving the flashover voltage of bushings when the equivalent salt deposit density (ESDD) was high. No obvious correlation was found between pollution flashover voltage and electric field stress. Furthermore, the uneven wetting flashover performance of the bushings was tested. Under this condition, the flashover voltage decreased with an increase of the electric field component vertical to the dielectric surface. In addition, the electric field distribution of the samples was calculated and the results were in accordance with the experimental results.