Comparison of thermal testing of MS9001FA type GTPs at shatura and nizhnevartovsk GRES

2016 
Domestic power plants use combined-cycle plants in which a gas-turbine plant (GTP) and a steam turbine rotate a common electric generator. In this instance, it is impossible to measure the power of each of them, so we have to resort to some assumptions. We have succeeded to check the validity of these assumptions and possible errors of their application testing combined-cycle plants (CCP) with the same GTP and a steam turbine but operating each on its own electrical generator. Comparative tests of a MS901FA GTP of the PGU-400 power-generating unit commissioned at Shatura GRES (a thermal power station) and a GTP of the same type installed at Nizhnevartovsk GRES were performed. As a result of these tests, dependences of the electric power of both gas-turbine plants and a turbine outlet temperature on the inlet temperature were obtained. A relation of the GTP efficiency, heat and air rate on the load are determined, and characteristics of compressors and turbines of both GTPs are defined. The performed tests have confirmed the accuracy of the determined characteristics of the two GTPs using both a direct measurement of net power (Nizhnevartovsk GRES) and an indirect measurement (Shatura GRES).